Generator Wattage Chart

AVERAGE WATTAGE REQUIREMENT GUIDE

(AMPS X VOLTS = WATTS)


Household


Running Wattage Requirements

Additional Wattage Required
For Starting

Coffee Maker 1750 0
Dishwasher Cool Dry 700 1400
Electric Fry Pan 1300 0
Electric Range 8-inch element 2100 0
Microwave Oven 625 watts 625 800
Refrigerator or Freezer 700 2200
Automatic Washer 1150 2300
Clothes Dryer Electric 5750 1800
Furnace Fan, gas or fuel oil
1/6 Horsepower 300 500
1/8 Horsepower 500 750
1/4 Horsepower 600 1000
1/3 Horsepower 700 1400
1/2 Horsepower 875 2350
Lights as indicated on bulb 0
Radio 50 to 200 0
Sump Pump
1/3 Horsepower 800 1300
1/2 Horsepower 1050 2150
Television - Color 300 0
Central Air Conditioner10,000 BTU 1500 2200
Contractor

Running Wattage Requirements

Additional Wattage Required
For Starting

Air Compressor 1 Horsepower 1500 4500
Bench Grinder 8 inches 1400 2500
Hand Drill 1/2 inch 600 0
High-pressure Washer 1 Horsepower 1200 3600
Circular Saw, Heavy Duty 71/4 inches 1400 2300
Electric Chain Saw 14 inches, 2 Horsepower 1100 0
Table Saw 10 inches 1800 4500
Drills
3/8 inch 4 amps 640 600
1/2 inch 5.4 amps 600 900
Industrial Motors

Running Wattage Requirements

Additional Wattage Required
For Starting

Split Phase
1/4 Horsepower 600 1000
1/2 Horsepower 875 2300
Capacitor Start Induction Run
1/3 Horsepower 720 1300
1 Horsepower 1600 4500
Capacitor Start Capacitor Run
1 1/2 Horsepower 2000 6100
Fan Duty1/4 Horsepower 650 1200
Farm Equipment

Running Wattage Requirements

Additional Wattage Required
For Starting

Electric Fence, 25 miles 250 0
Milk Cooler 1100 1800
Milker (vacuum pump), 2 Horsepower 1000 2300
Portable Heater (kerosene, diesel fuel)
50,000 BTU 400 600
90,000 BTU 500 725
150,000 BTU 625 1000
Battery Charger
15 amp 380 0
60 amp with 250-amp boost 1500/5750 0
100 amp with 300-amp boost 2400/7800 0
Electric Welder
200 amp AC 9000 0
230 amp AC, at 100 amp 7800 0
Air Compressors

Running Wattage Requirements

Additional Wattage Required
For Starting

1/2 Horsepower 975 1600
1 Horsepower 1600 4500
Computers

Running Wattage Requirements

Additional Wattage Required
For Starting

Desktop 600 to 800 0
Laptop 200 to 250 0
Monitor 200 to 250 0
Fax 600 to 800 0
Printer 400 to 600 0
 

 

The Eardly T. Petersen Co., Inc.
224 Elmer St., Westfield, NJ 07090 USA
toll-free 1-866-Peterco  fax 908-232-8761
www.etpetersen.com  e-mail: sales@etpetersen.com  
- since 1956 -